Article-No: 24 24 00
IEC category: Type 2 + 3 / class II + III
Nominal voltage DC: 24 V=
Nominal voltage AC: 17 V~
Max. continuous operating voltage DC: 27 V=
Max. continuous operating voltage AC (50/60Hz): 20 V~
Max. operating current: 6 A
Leakage current at Uc DC: ≤ 5 µA
DC resistance: 27 Ω
Series inductance, typ: 20 µH
Protection level line-earth at 1kV/μs and In: ≤ 800, typ. 650 V
Protection level line-line at 1 kV/µs and In: ≤ 37 / 55 V
Short-circuit current extinguishing capacity line-line: ≤ 6 A
Short-circuit current extinguishing capacity line-earth: ≤ 1 A
Lightning impulse current (10/350 µs): 3 kA
Nominal impulse discharge current (10 x 8/20 µs): 20 kA
Service life test current (500 x 10/700 µs): 200 A
Critical discharge current (10/700 µs): 1000 A
Max. alternating discharge current (50 Hz/ 5x 0,5s): 50 A
Max. current 50 Hz/0.5 s: 80 A
Operating temperature range: -25 – +85°C
Max. conductor cross section: 2.5 mm² single-wire / 1.5 mm² flexible with sleeve